Abstract: Commercial building HVAC systems (shopping malls, office towers, hotels, etc.) commonly suffer from declining cooling efficiency, rising energy consumption, and deteriorating indoor air quality due to prolonged operation and neglected maintenance. This article provides a systematic overview of maintenance technologies for both absorption chillers and centrifugal chillers, covering chemical cleaning, physical cleaning, water quality management, cooling tower descaling, and air duct disinfection. A real-world case study demonstrates the performance recovery achievable through structured preventative maintenance.

1. Operational Characteristics and Maintenance Challenges

Commercial building central AC systems typically operate year-round, with cooling seasons lasting 6 to 8 months. Hotels, hospitals, and data centers may run continuously 365 days a year. Compared to industrial HVAC systems, commercial AC maintenance faces three distinct challenges:

First, wide load fluctuations. Occupancy density in malls and office buildings varies dramatically by season and time of day. Chillers run at partial load for extended periods, causing LiBr solution concentration drift and frequent compressor cycling, which accelerates heat exchanger tube scaling and mechanical wear.

Second, weak water quality management. Most commercial properties outsource cooling water treatment, leading to inconsistent chemical dosing and blowdown. When the concentration cycle exceeds 5.0, CaCO₃ rapidly precipitates onto condenser tube walls—every 0.1 mm of scale reduces heat transfer efficiency by approximately 8%.

Third, air duct dust accumulation. Fresh air systems in malls and offices accumulate dust, fibers, and microbial biofilm over years without cleaning. China's national hygiene standard requires duct surface dust loading below 20 g/m², yet many commercial buildings exceed this by 3 to 5 times, creating breeding grounds for Legionella and other pathogens.

2. Chiller Classification and Targeted Maintenance

2.1 LiBr Absorption Chillers

Absorption chillers are widely used in large malls and hotels, driven by steam or hot water with no mechanical compressor. Key maintenance focuses on absorber and evaporator tube bundles and LiBr solution quality. After extended operation, scale on the outer tube wall increases the approach temperature; the COP can drop from the rated 1.3 to below 0.9, increasing steam consumption by over 30%.

Chemical cleaning protocol: Circulate 5%–8% Sulfamic Acid with 0.3% BTA corrosion inhibitor through condenser-side copper tubes at 40–50°C for 4–6 hours. For absorber-side stainless steel tubes, use Citric Acid (3%–5%) with Sodium Molybdate (0.2%) for passivation cleaning—simultaneous descaling and anodic protection film formation. After cleaning, sample the LiBr solution: pH below 9.0 or lithium content deviation exceeding ±2% requires replenishment or regeneration.

2.2 Centrifugal/Screw Chillers

Centrifugal and screw chillers dominate premium office buildings and hospitals. Maintenance priorities are condenser copper tube descaling and evaporator chilled-water-side biofilm removal. The condenser approach temperature (difference between condensing temperature and cooling water outlet temperature) is the key diagnostic metric: normal is ≤3°C; exceeding 5°C indicates ≥0.3 mm CaCO₃ scale requiring chemical cleaning.

Cleaning formula and procedure:

Step Chemical Concentration Temp/Time Purpose
DegreasingNa₂CO₃ + Surfactant2% + 0.1%60°C / 2hRemove oil and biofilm
Acid washSulfamic Acid + BTA5%–8% + 0.3%45°C / 4–6hRemove CaCO₃ and rust
RinseCitric Acid0.5%Ambient / 1hRemove residual iron ions
PassivationNaNO₂ + Na₃PO₄1% + 0.5%Ambient / 2hForm protective film

3. Cooling Tower and Air Duct Maintenance

3.1 Cooling Tower Descaling and Microbial Control

Cooling towers are the most neglected component of central AC systems. Cooling water contacts ambient air directly in the tower, continuously ingesting dust, bacteria, and algae. When fill media becomes fouled, the tower's heat rejection capacity drops by 20%–40%, directly raising condensing pressure and chiller energy consumption.

Cooling tower maintenance should be performed quarterly: high-pressure water jetting (15–25 MPa) to clean fill media and distribution nozzles, removing scale and algae; draining sediment from the basin; shock dosing with non-oxidizing biocide (Isothiazolinone class, 50–100 mg/L). Remove debris and obstructions around the tower to ensure unobstructed airflow.

3.2 Air Duct Cleaning and Disinfection

Commercial building duct systems extend thousands of meters across supply, return, and fresh air pathways. Duct cleaning employs mechanical brushing combined with negative-pressure dust collection: motorized rotating brushes dislodge wall deposits while high-power negative-pressure collectors simultaneously extract airborne dust, preventing secondary contamination. After cleaning, hydrogen peroxide vapor (H₂O₂ 3%–5% atomized) or quaternary ammonium disinfectants are applied for bacterial and fungal decontamination.

Duct cleaning is measured by surface area—typically 2,000–3,000 m² of ductwork per 10,000 m² of building floor area. A full cleaning cycle is 3–5 years, shortened to 2 years for high-traffic malls and high-humidity hotels.

4. Water Quality Management and Preventative Maintenance

Chemical cleaning addresses existing scale; water quality management prevents it from forming. Commercial building AC water systems comprise circulating cooling water and chilled water loops, with the following quality control targets:

Parameter Cooling Water (Open) Chilled Water (Closed)
pH7.0–9.08.0–10.0
Conductivity (μS/cm)≤2,000≤800
Total Hardness (mg/L CaCO₃)≤400≤150
Total Iron (mg/L)≤1.0≤0.5
Chloride (mg/L)≤300≤50
Total Bacteria (CFU/mL)≤10⁵≤10³

Daily operation should employ a three-component treatment: Polyacrylic Acid (10–20 mg/L) to inhibit CaCO₃ crystal growth, organophosphonate (5–10 mg/L) for corrosion inhibition, and alternating oxidizing (sodium hypochlorite, residual chlorine 0.5–1.0 mg/L for 2h) and non-oxidizing biocides to prevent microbial resistance. Weekly water sampling with dynamic dose adjustment is essential.

5. Case Study: Mixed-Use Commercial Complex AC Maintenance

Project overview: A mixed-use commercial complex of approximately 120,000 m², comprising a shopping mall, office tower, and five-star hotel. HVAC configuration: 3 absorption chillers (total 10,500 kW) + 2 centrifugal chillers (total 7,000 kW), 6 cooling towers, and ~26,000 m² of ductwork. After 8 years of operation, cooling performance had declined for two consecutive years; chilled water supply temperature during peak summer could only reach 12–14°C (design: 7°C), with frequent hotel guest complaints.

Diagnostic findings: Condenser approach temperature 7.2°C (normal ≤3°C); CaCO₃ scale thickness 0.5–0.8 mm on copper tube inner walls; LiBr solution pH dropped to 8.6 with partial crystallization; cooling tower fill heavily fouled with uneven water distribution; duct dust loading 87 g/m², 4.3× over the standard; cooling water concentration cycle 7.8, iron 3.2 mg/L.

Maintenance implementation: Phase 1 (pre-cooling-season) — chemical cleaning of 3 absorption chiller absorbers/condensers and LiBr solution regeneration, 6 days; Phase 2 — descaling and passivation of 2 centrifugal chiller condensers; Phase 3 — high-pressure cleaning and algicide treatment of 6 cooling towers plus full duct cleaning and disinfection; Phase 4 — installation of automated water treatment dosing system with conductivity-controlled blowdown interlock.

Results: Chilled water supply temperature restored to 7.2°C; system COP improved from 0.88 to 1.25; summer electricity consumption decreased 27%, saving approximately ¥860,000 annually. All indoor air quality parameters met standards; hotel complaints dropped to zero. The system has since been on quarterly preventative maintenance for three consecutive years with no cooling degradation from scaling.

6. Maintenance Scheduling and Summary

Commercial building central AC maintenance should be institutionalized and scheduled, not left to reactive emergency cleaning when performance collapses. Recommended maintenance intervals by equipment type: chiller chemical cleaning every 1–2 years (extendable with good water treatment); cooling tower high-pressure wash and biocide treatment quarterly; air duct comprehensive cleaning and disinfection every 3–5 years (2 years for high-traffic buildings); weekly water quality testing with chemical dose adjustment.

In summary, commercial building HVAC maintenance is a systems engineering challenge—chiller cleaning restores heat transfer efficiency, cooling tower maintenance ensures heat rejection capacity, water quality management prevents scale at the source, and duct disinfection protects indoor air quality. All four pillars are essential. Facility managers must abandon the "fix-when-broken" mindset and adopt a prevention-first scientific maintenance model, transforming the central AC system from an energy black hole into a benchmark of efficiency.

All acceptance criteria follow GB/T 25146-2010 Quality acceptance specifications of chemical cleaning for industrial equipment.

Commercial HVAC Maintenance · Free Technical Consultation

Absorption Chiller Cleaning | Centrifugal Chiller Descaling | Cooling Tower Treatment | Air Duct Disinfection

📞 +86 18952832843

Danyang Lanxing Anticorrosion Cleaning Co., Ltd. · Member of China Industrial Cleaning Association · China Boiler & Boiler Water Treatment Association
Address: 98 Hongjiadai, Picheng, Danbei Town, Danyang City, Jiangsu · Email: luohuiyong@126.com

Service Coverage: Jiangsu (Nanjing, Suzhou, Wuxi, Changzhou, Zhenjiang, Yangzhou) · Zhejiang (Hangzhou, Ningbo) · Shanghai · Anhui (Hefei) · Shandong · Henan

© 2026 Danyang Lanxing Anticorrosion Cleaning Co., Ltd. All Rights Reserved | Source: www.lanxingqingxi.com